R-22 Replacement Options: A Contractor's Guide

R-22 Replacement Options: A Contractor's Guide

New production and import of R-22 (HCFC-22) ended on January 1, 2020, but existing and reclaimed R-22 can still be used to service equipment built for it. If you have an R-22 system, you have three choices: keep servicing it with R-22, retrofit it with an EPA-listed substitute, or replace the system. This guide covers each and links to EPA.

R-22 legal status

Date EPA Class II phaseout schedule
January 1, 2010 No production or import of HCFC-22 and HCFC-142b, except for use in equipment manufactured before January 1, 2010.
January 1, 2020 No production or import of HCFC-22 and HCFC-142b.
2030 Complete HCFC phaseout under the Montreal Protocol schedule.

Used refrigerant can only be sold for use in an appliance if it has been reclaimed by an EPA certified reclaimer.

Option 1: keep servicing with R-22

Servicing with existing or reclaimed R-22 is allowed. R-22 is available from Refrigerant Inc in cylinders from 2 lb to 30 lb to EPA Section 608 certified technicians and buyers who employ one. Fix leaks first. A system that keeps losing charge costs more to run than the refrigerant alone.

Option 2: retrofit with an EPA-listed substitute

EPA's SNAP program lists acceptable substitutes by end use. These R-22 substitutes sold by Refrigerant Inc appear as acceptable in EPA's SNAP table for residential and light commercial air conditioning and heat pumps (table last updated March 19, 2026):

Substitute Trade names in EPA table Listing GWP (EPA table) Product
R-407C Suva 407C, Klea 407C Retrofit and new 1,770 R-407C
R-422B ICOR XAC1, NU-22B Retrofit and new 2,530 R-422B
R-422D ISCEON MO29 Retrofit and new 2,730 R-422D
R-434A RS-45 Retrofit and new 3,250 RS-45
R-438A KDD5, ISCEON MO99 Retrofit and new 2,270 R-438A (MO99)

SNAP acceptability applies to a specific substitute in a specific end use. For any other R-22 replacement blend, including R-453A (RS-44b) and R-470A or R-470B (RS-51, RS-53), confirm the SNAP status for your equipment type from the manufacturer's documentation and EPA's list before you use it.

How a retrofit works

  1. Recover the R-22 charge. Do not mix refrigerants.
  2. Follow the substitute manufacturer's retrofit procedure. It states what oil to use, whether seals or a filter drier should be changed, and how to charge. Substitute blends are not true drop-ins, and charging a blend usually means charging as a liquid.
  3. Charge, then verify. Check pressures and temperatures against the manufacturer's pressure-temperature data. Expect capacity and efficiency to differ somewhat from the original R-22 charge.
  4. Label the equipment with the new refrigerant, charge and date.

Option 3: replace the system

New residential and light commercial air conditioning and heat pump systems use refrigerants with a GWP of 700 or less, including A2L refrigerants such as R-32 and R-454B. These refrigerants are for new equipment only and cannot be used to retrofit an R-22 or R-410A system. See the R-410A to A2L transition guide.

Which option fits?

Situation Consider
Minor leak that can be found and fixed Repair and recharge with R-22.
Repeated leaks or a major component failure Ask whether a retrofit or a replacement makes sense. Get the equipment maker's guidance.
Equipment past its expected life Replacement with new equipment.

Not sure which refrigerant fits? Use our interactive replacement guide, or call 888-593-7366.

R-22 replacement FAQ

Is R-22 still legal to use?

Yes, for servicing existing equipment. EPA's table of the Class II ozone-depleting substance phaseout lists no production or import of R-22 beginning January 1, 2020. Existing and reclaimed R-22 can still be sold and used to service equipment built for it.

Can I top off an R-22 system with a replacement blend?

No. Recover the existing R-22 charge before you introduce a replacement. Mixing refrigerants creates a blend that cannot be reliably identified or serviced.

Is any R-22 replacement a drop-in?

Treat none as a true drop-in. Substitute manufacturers publish retrofit procedures that can include an oil change, seal replacement and charging the blend as a liquid. Follow the procedure for the specific product, and confirm EPA SNAP acceptability for your equipment type.

Can I put R-32 or R-454B in an R-22 system?

No. EPA lists R-32 and R-454B for new equipment designed for them. They are not retrofit refrigerants for R-22 or R-410A systems.

Do I need EPA certification to buy R-22 or a replacement?

Refrigerant Inc sells to EPA Section 608 certified technicians and to buyers who employ one. EPA's guidance on the refrigerant sales restriction says sellers, including online sellers, must verify this and keep invoices for three years.

When is the R-22 phaseout complete?

EPA's Class II phaseout table shows a complete HCFC phaseout in 2030 under the Montreal Protocol schedule, with production and import of R-22 already ended in 2020.